Baseboard heater calculator: what size baseboard heater do I need?

1 heater: 1,500 W, 6 ft

1,440 W needed at 10 W per sq ft, King K Series at 240 V · 6.3 A: 1 circuit on a 15 A breaker (12 A at 80%) · for a 12 × 12 ft room

Run your own numbers

Enter it the way you measured it: 4.5, 4 1/2, 3/8 or 10' 6".

1 heater: 1,500 W, 6 ft

1,440 W needed at 10 W per sq ft, King K Series at 240 V · 6.3 A: 1 circuit on a 15 A breaker (12 A at 80%)

    Source: Cadet, Installing electric heaters: 6 to 10 watts per square foot, read October 31, 2026. Read the source

    A 12 × 12 ft room at 10 watts per sq ft, the top of Cadet's 6 to 10 range, needs 1,440 W: one 1,500 W, 6 ft baseboard heater at 240 V, 6.3 A, under the 12 A Cadet allows per 15 A breaker.

    A worked example

    A 14 ft 6 in × 21 ft living room at 9 W per sq ft, on a 208 V supply with 15 A breakers and King heaters, needs two heaters, 2,400 W, 8 ft (1,800 W at 208 V) + 1,500 W, 6 ft (1,125 W at 208 V), on two 15 A circuits. 14.5 × 21 ft is 304.5 sq ft, and at 9 W that is 2,741 W. On 208 V a King 240 V heater gives 25% less, so the 2,400 W and 1,500 W models give 2,925 W together: 14.1 A, over the 12 A that 80% of one 15 A breaker allows.

    How many baseboard heaters on a 20 amp circuit?

    As many as stay within 80% of the breaker, Cadet's limit: 16 A on a 20 A breaker, or 3,840 W of heaters at 240 V, such as a 2,000 W and a 1,500 W. A 15 A breaker takes 12 A, 2,880 W. A thermostat rated lower sets the cap.

    How many watts per square foot for baseboard heat?

    Cadet recommends 6 to 10 W per sq ft, by the home's construction, the region and whether the heaters are the only heat: 900 to 1,500 W for a 150 sq ft room.

    How many watts is an 8 foot baseboard heater?

    2,000 or 2,400 W in King's K Series and 2,000 or 2,500 W in Marley's 2500 Series, at 240 V. On 208 V they give 25% less: 1,500 or 1,800 W for King. A 6 ft heater is 1,500 W in both lines.

    What else it is called

    Also searched as a baseboard heat calculator, baseboard heating calculator, baseboard heater size or wattage calculator, or electric baseboard heat calculator. This one is for electric heaters; hot water (hydronic) baseboard is sized by Btu per foot of element.

    Heaters by room size

    King K Series 240 V baseboard heaters and amps by room size at 6, 8 and 10 watts per square foot, the range Cadet recommends
    RoomAt 6 W per sq ftAt 8 W per sq ftAt 10 W per sq ft
    10 × 10 ft (100 sq ft) 750 W, 3 ft (3.1 A)1,000 W, 4 ft (4.2 A)1,000 W, 4 ft (4.2 A)
    10 × 12 ft (120 sq ft) 750 W, 3 ft (3.1 A)1,000 W, 4 ft (4.2 A)1,250 W, 5 ft (5.2 A)
    12 × 12 ft (144 sq ft) 1,000 W, 4 ft (4.2 A)1,250 W, 5 ft (5.2 A)1,500 W, 6 ft (6.3 A)
    12 × 14 ft (168 sq ft) 1,250 W, 5 ft (5.2 A)1,500 W, 6 ft (6.3 A)2,000 W, 8 ft (8.3 A)
    14 × 16 ft (224 sq ft) 1,500 W, 6 ft (6.3 A)2,000 W, 8 ft (8.3 A)2,400 W, 8 ft (10.0 A)
    16 × 20 ft (320 sq ft) 2,000 W, 8 ft (8.3 A)2,000 W, 8 ft + 750 W, 3 ft (11.5 A)2,000 W, 8 ft + 1,250 W, 5 ft (13.5 A)

    Heaters from the King K Series 240 V list (500 W 27 in; 750, 1,000, 1,250 and 1,500 W at 3, 4, 5 and 6 ft; 2,000 and 2,400 W at 8 ft), the fewest pieces that reach the watts; amps at 240 V. Cadet recommends 6 to 10 W per sq ft and at most 80% of the breaker on one circuit: 12 A on 15 A, 16 A on 20 A.

    Where the numbers come from

    Watts per square foot is the one sizing input: Cadet's range already spans construction, region and whether the heaters are the only heat. Watts and lengths are the catalog's 240/208 V models; 120 V models are left out. The 80% check counts the heaters alone, on circuits that feed nothing else.