Conduit fill calculator: how many wires fit in a conduit?

9 wires

12 AWG THHN in 1/2 in EMT · 3/4 in takes 16 · IRC 2021 Table E3904.6(1) · for wires of one size and type

Run your own numbers

Enter it the way you measured it: 4.5, 4 1/2, 3/8 or 10' 6".

9 wires

12 AWG THHN in 1/2 in EMT · 3/4 in takes 16 · IRC 2021 Table E3904.6(1)

    Source: IRC 2021 Section E3904.6 and Tables E3904.6(1) to (10), Maximum Number of Conductors in conduit and tubing (International Code Council; NEC Annex C), read November 3, 2026. Read the source

    A 1/2 inch EMT conduit holds 9 wires of 12 AWG THHN or THWN-2 by IRC 2021 Table E3904.6(1); 3/4 inch EMT holds 16, and 14 AWG fits 12 in 1/2 inch.

    A worked example

    Seven 10 AWG THHN wires in Schedule 40 PVC needs 3/4 in conduit. 1/2 in Schedule 40 PVC takes 5 wires of 10 AWG THHN and 3/4 in takes 9, by IRC 2021 Table E3904.6(10). In 1/2 in EMT the same wire fits 5 too, so the bore of the tubing, not the wire, decides the size.

    How many wires in 3/4 EMT?

    22 of 14 AWG, 16 of 12 AWG, 10 of 10 AWG and 6 of 8 AWG THHN or THWN-2, by IRC 2021 Table E3904.6(1). In XHHW the 3/4 in counts are 15, 11 and 8 for 14, 12 and 10 AWG.

    How many wires in 1/2 conduit?

    In 1/2 in EMT, 12 of 14 AWG, 9 of 12 AWG and 5 of 10 AWG THHN. In 1/2 in Schedule 40 PVC, 11, 8 and 5; in Schedule 80 PVC, 9, 6 and 4, because its wall is thicker and the bore smaller.

    How many wires in 3/4 PVC conduit?

    Schedule 40: 21 of 14 AWG, 15 of 12 AWG and 9 of 10 AWG THHN (Table E3904.6(10)). Schedule 80: 17, 12 and 7 (Table E3904.6(9)).

    What else it is called

    Also searched as how many wires in 3/4 conduit, how many wires in 1/2 conduit, how many wires in 3/4 EMT or a conduit fill chart. The count includes every conductor in the conduit, grounds too, and the type letters are the ones printed on the wire jacket.

    Wires per conduit size

    Maximum THHN and THWN-2 wires of one size in EMT and in PVC Schedule 40 conduit, 1/2 to 2 in, IRC 2021 Tables E3904.6(1) and (10)
    THHN or THWN-21/2 in3/4 in1 in1 1/4 in1 1/2 in2 in
    1 AWG in EMT 111458
    2 AWG in EMT 1135711
    3 AWG in EMT 1136813
    4 AWG in EMT 12471016
    6 AWG in EMT 247121626
    8 AWG in EMT 369162236
    10 AWG in EMT 51016283863
    12 AWG in EMT 916264561101
    14 AWG in EMT 1222356184138
    1/0 AWG in EMT 111347
    2/0 AWG in EMT 011236
    3/0 AWG in EMT 011135
    4/0 AWG in EMT 011124
    14 AWG in PVC Schedule 40 1121346082135
    12 AWG in PVC Schedule 40 81525435999
    10 AWG in PVC Schedule 40 5915273762
    8 AWG in PVC Schedule 40 359162136
    6 AWG in PVC Schedule 40 146111526

    Maximum number of conductors of one size and type, IRC 2021 Table E3904.6(1), electrical metallic tubing, and Table E3904.6(10), rigid PVC conduit Schedule 40 (NEC Annex C, Tables C.1 and C.10), as printed. The other eight tubing types and the TW, THW, XHHW and RHW columns are in the calculator above.

    Where the numbers come from

    The tables are for wires of one size and one type. Mixed sizes in one conduit need the wire and conduit areas of NEC Chapter 9, Tables 4 and 5, which the IRC does not print, so they are not in this calculator. Neither are data cable or conduit over 2 in.