Drain pipe slope calculator: how much slope does a drain pipe need?

5 in of fall

1/8 in per ft (1.04%), the 3 in pipe minimum · for a 40 ft run

Run your own numbers

Enter it the way you measured it: 4.5, 4 1/2, 3/8 or 10' 6".

5 in of fall

1/8 in per ft (1.04%), the 3 in pipe minimum

    Source: International Plumbing Code 2021, Section 704.1 and Tables 704.1 and 710.1(1), read October 27, 2026. Read the source

    A 3 in drain pipe must fall at least 1/8 in per foot by IPC 2021 Table 704.1, so a 40 ft run drops 5 in; pipe of 2 1/2 in or less takes 1/4 in per foot and 8 in or larger 1/16.

    A worked example

    A 4 in building drain carrying 190 drainage fixture units over a run of 37 ft 6 in needs 9 3/8 in of fall. Table 704.1 asks 1/8 in per ft of a 4 in pipe, but Table 710.1(1) lets it carry only 180 DFU at that slope; at 1/4 in per ft it carries 216. So the run falls 37.5 × 1/4 = 9.375 in, marked as 9 3/8 in.

    What is the minimum slope per foot for a drain pipe?

    By IPC 2021 Table 704.1: 1/4 in per ft for pipe of 2 1/2 in or less, 1/8 in for 3 to 6 in, and 1/16 in for 8 in and larger. Over 10 ft that is 2 1/2 in, 1 1/4 in and 5/8 in of fall.

    What is 1/4 inch per foot in percent?

    About 2 percent, as the code itself writes it in 704.1: 0.25 ÷ 12 is 2.08%. 1/8 in per ft is 1.04% and 1/16 in per ft 0.52%.

    Does more slope let a drain carry more?

    Yes, on a building drain: Table 710.1(1) lets a 4 in drain carry 180 fixture units at 1/8 in per ft, 216 at 1/4 and 250 at 1/2. A 3 in drain goes from 36 to 42 to 50.

    What else it is called

    Also searched as drain pipe slope per foot, sewer pipe slope calculator or drain fall calculator. Plumbers say fall or pitch; the code says slope, in inches per foot.

    The full IPC tables

    Minimum slope of horizontal drainage pipe (IPC 2021 Table 704.1) and building drain fixture units by size and slope (Table 710.1(1))
    PipeMinimum slopeFall per 10 ftDFU at 1/16 in/ftat 1/8at 1/4at 1/2
    1 1/4 in 1/4 in per ft2 1/2 in——11
    1 1/2 in 1/4 in per ft2 1/2 in——33
    2 in 1/4 in per ft2 1/2 in——2126
    2 1/2 in 1/4 in per ft2 1/2 in——2431
    3 in 1/8 in per ft1 1/4 in—364250
    4 in 1/8 in per ft1 1/4 in—180216250
    5 in 1/8 in per ft1 1/4 in—390480575
    6 in 1/8 in per ft1 1/4 in—7008401,000
    8 in 1/16 in per ft5/8 in1,4001,6001,9202,300
    10 in 1/16 in per ft5/8 in2,5002,9003,5004,200
    12 in 1/16 in per ft5/8 in3,9004,6005,6006,700
    15 in 1/16 in per ft5/8 in7,0008,30010,00012,000

    Minimum slope: IPC 2021 Table 704.1, for all horizontal drainage pipe; 1/4 in per ft upstream of a grease interceptor. Drainage fixture units: Table 710.1(1), the most a building drain or building sewer of that size carries at each slope; — means the size is not listed at that slope. A building drain serving a water closet is at least 3 in.

    Where the numbers come from

    The slopes are the IPC minimums. The Uniform Plumbing Code, used instead of the IPC in some states, is another code and is not included. The fixture unit check is for building drains and sewers; horizontal fixture branches use Table 710.1(2), with no slope column.

    By · Last updated . How this site is made.