Wire size calculator: what size wire do I need for my amps?

6 AWG copper

55 A at 60 °C, Table E3705.1 · in aluminum, 4 AWG · for a 50 A circuit in NM cable

Run your own numbers

Enter it the way you measured it: 4.5, 4 1/2, 3/8 or 10' 6".

6 AWG copper

55 A at 60 °C, Table E3705.1 · in aluminum, 4 AWG

    Source: IRC 2021 Table E3705.1, Allowable Ampacities, with Sections E3705.4.1, E3705.4.2 and E3705.4.4 and Table E3705.5.3 (International Code Council), read November 3, 2026. Read the source

    A 50 amp circuit in NM cable (Romex) needs 6 AWG copper, rated 55 amps in the 60 °C column of IRC 2021 Table E3705.1; in aluminum it is 4 AWG.

    A worked example

    A 70 amp feeder in aluminum THHN to a garage subpanel needs 2 AWG aluminum. At 70 A the terminals count at 60 °C (Section E3705.4.1), where 4 AWG aluminum carries 55 A and 3 AWG 65 A, so the first that reaches 70 is 2 AWG at 75 A. With equipment marked 75 °C it would be 3 AWG, at 75 A.

    What size wire for a 30 amp breaker?

    10 AWG copper: Table E3705.5.3 allows a 30 A breaker on 10 AWG and no larger, and 10 AWG carries 30 A at 60 °C. In aluminum, 8 AWG, which the same table caps at 30 A.

    What size wire for a 60 amp breaker?

    4 AWG copper in NM cable, 70 A at 60 °C; 6 AWG copper reaches only 55 A there. With THHN in conduit and equipment marked 75 °C, 6 AWG copper carries 65 A and is enough.

    What size wire for 100 amps?

    At 100 A or less the terminals count at 60 °C unless the equipment is marked otherwise: 1 AWG copper (110 A) or 1/0 aluminum (100 A). With 75 °C terminals, 3 AWG copper or 1 AWG aluminum, both 100 A.

    What else it is called

    Also searched as a wire gauge calculator, an electrical wire size calculator, what size wire for 50 amp, what size wire for a 30 amp breaker or an ampacity chart. AWG numbers run backwards: the smaller the number, the thicker the wire.

    Ampacity chart

    Allowable ampacity of copper and aluminum wire 14 AWG to 500 kcmil at 60, 75 and 90 °C, IRC 2021 Table E3705.1, with the small conductor breaker limits
    SizeCopper 60 °CCopper 75 °CCopper 90 °CAluminum 60 °CAluminum 75 °CAluminum 90 °C
    14 AWG 15 (15)20 (15)25 (15)———
    12 AWG 20 (20)25 (20)30 (20)15 (15)20 (15)25 (15)
    10 AWG 30 (30)35 (30)40 (30)25 (25)30 (25)35 (25)
    8 AWG 40505535 (30)40 (30)45 (30)
    6 AWG 556575405055
    4 AWG 708595556575
    3 AWG 85100115657585
    2 AWG 951151307590100
    1 AWG 11013014585100115
    1/0 AWG 125150170100120135
    2/0 AWG 145175195115135150
    3/0 AWG 165200225130155175
    4/0 AWG 195230260150180205
    250 kcmil 215255290170205230
    300 kcmil 240285320195230260
    350 kcmil 260310350210250280
    400 kcmil 280335380225270305
    500 kcmil 320380430260310350

    Allowable ampacity in amps, IRC 2021 Table E3705.1, not more than three current-carrying conductors at 30 °C (86 °F). In brackets, the largest breaker Table E3705.5.3 allows on 14, 12 and 10 AWG copper and 12, 10 and 8 AWG aluminum. NM cable stays in the 60 °C column (Section E3705.4.4), and so do circuits of 100 A or less unless the equipment is marked otherwise (E3705.4.1).

    Where the numbers come from

    The ampacities are for up to three current-carrying conductors at 30 °C (86 °F). Hotter spaces and bundles of more conductors take the factors of Sections E3705.2 and E3705.3, voltage drop over long runs needs conductor resistances the IRC does not print, and dwelling services sized by the 83 percent rule of Table E3603.1 are not in this calculator.